Test Conclusions
If the following conditions are met the performance may be considered normal. If they are not met refer to the diagnosis charts. See Figure .
- Discharge air temperature should agree with the value shown on the performance charts within ±3°F.
- High side gauge pressure should agree with the value shown on the performance charts within 25 psi.
- Except where ambient temperature and humidity are extremely high, low side gauge pressure should in all cases be 29 psi. ±2 psi.